A C D E F G H I J K
1 EUI EUI kWh/m²/a       Year Month   Month
2   Reference All-Electric Facility 780       2024 #REF!    
3   BAWC 619              
4   Increased Efficiency 21% EUI BAWC vs Reference All-Electric Facility          
7 Facility_Level Facility Level MWh kgCO2            
8   Total Energy 503.586 8,590.20            
9   Total Electricity 460.515 0.00 Gas: 460.514795MWh, 0 kgCO2e        
10   Grid Electricity 433.901 0.00 Grid Electricty: 433.901095MWh, 0 kgCO2e        
11   Solar Electricity 26.614 0.00            
12   Gas Consumption 43.072 8,590.20            
14 WeeklyGHG Weekly Total GHG Emissions [kgCO2e]              
15   1 4671.562896              
16   2 1313.342316              
17   3 211.760406              
18   4 1217.087586              
21 Thermal_Plant Energy Input & Output CH1 CH2 CH3          
22   Energy Input (Electricity) -35.537125 -36.167759 -88.50116          
23   Energy Output (Heating) 79.78 117.81 265.44          
24   Energy Output (Cooling) 7.14 0.01 0.00          
26 Thermal_Plant_Boiler Energy Input & Output Boiler              
27   Energy Input (Gas) 43.0716              
28   Energy Output (Heating) 36.611              
30 WeeklyGas Weekly Gas Consumption [m³]   Days Min Temp Week1 Week2 Week3 Week4  
31   1 2443   Days Min. Temp above 10 °C 0 0 0 1  
32   2 616   Days Min. Temp between 10°C - 5°C 2 6 7 1  
33   3 99   Days Min. Temp below 5 °C 5 1 0 5  
34   4 720              
36 Solar Solar PV Electricty MWh              
37   Solar PV Electricty Produced 26.614              
38   Solar PV Electricty Used by Facility 26.614              
39   Solar PV Electricty Exported to the Grid 0.000              
40   Specific Yield Solar 1.561              
41   Share of Total Electricity Demand 0.058              
43 WeeklySolar Weekly PV Grid            
44   1 7111.5 100,334            
45   2 5403.4 96,773            
46   3 5987.7 100,220            
47   4 7487.7 94,325            
49 Thermal_Energy Thermal Energy Storage MWh Notes3            
50   Thermal Output 4.61              
51   Thermal Input 15.905002              
52   Roundtrip Efficiency Roundtrip Efficiency: 29%              
56 Thermal_Plant_value Thermal Plant Electricty Input Thermal Output Heating Thermal Output Cooling COP Share of Total Thermal Output      
57   CH1 -35.54 79.78 7.14 2.44589066 0.172      
58   CH2 -36.17 117.81 0.01 3.25759249 0.232      
59   CH3 -88.50 265.44 0.00 2.99928204 0.524      
61   Thermal Plant Thermal Output Gas Input Efficiency Share of heating output Notes1 Notes2    
62 Boiler Boiler 36.61086 43.0716 0.85 7.2% Estimate only, thermal energy meter at the boiler currently not calibrated Estimate only, thermal energy meter at the boiler currently not calibrated
66 Site_Demand Energy Demand kVW              
67   Max Demand 954              
68   Average Demand 582